Motor Nominal Power (kW) 380/400V, 50/60Hz | Thermal Adjustment Area (A) | Schneider Motor Protection Switch Reference code | Schneider Contactor Reference Code Coil Voltage 220V AC 50/60 Hz |
0.06 | 0.16...0.25 | GV2ME02 | LC1D09M7 |
0.09 | 0.25...0.40 | GV2ME03 | LC1D09M7 |
0.12 | 0.40...0.63 | GV2ME04 | LC1D09M7 |
0.18 | 0.40...0.63 | GV2ME04 | LC1D09M7 |
0.25 | 0.63...1 | GV2ME05 | LC1D09M7 |
0.37 | 1...1.6 | GV2ME06 | LC1D09M7 |
0.55 | 1...1.6 | GV2ME06 | LC1D09M7 |
0.75 | 1.6...2.5 | GV2ME07 | LC1D09M7 |
1.1 | 2.5....4 | GV2ME08 | LC1D09M7 |
1.5 | 2.5...4 | GV2ME08 | LC1D09M7 |
2.2 | 4...6.3 | GV2ME10 | LC1D09M7 |
3 | 6...10 | GV2ME14 | LC1D09M7 |
3.7 | 6...10 | GV2ME14 | LC1D09M7 |
4 | 6...10 | GV2ME14 | LC1D09M7 |
5.5 | 9...14 | GV2ME16 | LC1D12M7 |
7.5 | 13...18 | GV2ME20 | LC1D18M7 |
9 | 17...23 | GV2ME21 | LC1D25M7 |
11 | 20...25 | GV2ME22 | LC1D25M7 |
15 | 24...32 | GV2ME32 | LC1D32M7 |
18.5 | 30...40 | GV3P40 | LC1D38M7 LC1D40AM7 |
22 | 37...50 | GV3P50 | LC1D50AM7 |
30 | 48...65 | GV3P65 | LC1D65AM7 |
37 | 62...73 | GV3P73 | LC1D80M7 |
45 | 50-100 | C10H32M100 | LC1D95M7 |
55 | 70-150 | C16H32M150 | LC1D115M7 |
75 | 70-150 | C16H32M150 | LC1D150M7 |
90 | 100-220 | GV5P220F (36kA) GV5P220H (70kA) | LC1G185KUEN |
110 | 100-220 | GV5P220F (36kA) GV5P220H (70kA) | LC1G225KUEN |
132 | 160-320 | GV6P320F (36kA) GV6P320H (70kA) | LC1G265KUEN |
160 | 160-320 | GV6P320F (36kA) GV6P320H (70kA) | LC1G330KUEN |
200 | 250...500 | GV6P500F (36kA) GV6P500H (70kA) | LC1G400KUEN |
220 | 250...500 | GV6P500F (36kA) GV6P500H (70kA) | LC1G500KUEN |
250 | 250...500 | GV6P500F (36kA) GV6P500H (70kA) | LC1G500KUEN |
315 | 250-630 | C63F32D630 (36kA) C63F35E630 (36kA) C63N32D630 (50kA) C63N35E630 (50kA) C63N36E630 (50kA) C63H32D630 (70kA) C63H35E630 (70kA) C63H36E630 (70kA) | LC1G630KUEN |
335 | 250-630 | C63F32D630 (36kA) C63F35E630 (36kA) C63N32D630 (50kA) C63N35E630 (50kA) C63N36E630 (50kA) C63H32D630 (70kA) C63H35E630 (70kA) C63H36E630 (70kA) | LC1G630KUEN |