Motor protection switch and contactor selection table according to motor nominal power (kW) and current value (Contactors are selected with 1NO+1NC auxiliary contact and 220 V AC coil voltage)

Writer's picture: R&D EngineerR&D Engineer

Updated: Oct 25, 2024

Motor Nominal Power (kW) 380/400V, 50/60Hz

Thermal Adjustment Area (A)

Schneider Motor Protection Switch Reference code

Schneider Contactor Reference Code Coil Voltage 220V AC 50/60 Hz

0.06

0.16...0.25

GV2ME02

LC1D09M7

0.09

0.25...0.40

GV2ME03

LC1D09M7

0.12

0.40...0.63

GV2ME04

LC1D09M7

0.18

0.40...0.63

GV2ME04

LC1D09M7

0.25

0.63...1

GV2ME05

LC1D09M7

0.37

1...1.6

GV2ME06

LC1D09M7

0.55

1...1.6

GV2ME06

LC1D09M7

0.75

1.6...2.5

GV2ME07

LC1D09M7

1.1

2.5....4

GV2ME08

LC1D09M7

1.5

2.5...4

GV2ME08

LC1D09M7

2.2

4...6.3

GV2ME10

LC1D09M7

3

6...10

GV2ME14

LC1D09M7

3.7

6...10

GV2ME14

LC1D09M7

4

6...10

GV2ME14

LC1D09M7

5.5

9...14

GV2ME16

LC1D12M7

7.5

13...18

GV2ME20

LC1D18M7

9

17...23

GV2ME21

LC1D25M7

11

20...25

GV2ME22

LC1D25M7

15

24...32

GV2ME32

LC1D32M7

18.5

30...40

GV3P40

LC1D38M7                   LC1D40AM7

22

37...50

GV3P50

LC1D50AM7

30

48...65

GV3P65

LC1D65AM7

37

62...73

GV3P73

LC1D80M7

45

50-100

C10H32M100

LC1D95M7

55

70-150

C16H32M150

LC1D115M7

75

70-150

C16H32M150

LC1D150M7

90

100-220

GV5P220F (36kA)   GV5P220H (70kA)

LC1G185KUEN

110

100-220

GV5P220F (36kA)   GV5P220H (70kA)

LC1G225KUEN

132

160-320

GV6P320F (36kA)    GV6P320H (70kA)

LC1G265KUEN

160

160-320

GV6P320F (36kA)    GV6P320H (70kA)

LC1G330KUEN

200

250...500

GV6P500F (36kA)    GV6P500H (70kA)

LC1G400KUEN

220

250...500

GV6P500F (36kA)    GV6P500H (70kA)

LC1G500KUEN

250

250...500

GV6P500F (36kA)    GV6P500H (70kA)

LC1G500KUEN

315

250-630

C63F32D630 (36kA)   C63F35E630 (36kA)    C63N32D630 (50kA)    C63N35E630  (50kA)   C63N36E630 (50kA)   C63H32D630 (70kA)   C63H35E630 (70kA)   C63H36E630 (70kA)

LC1G630KUEN

335

250-630

C63F32D630 (36kA)   C63F35E630 (36kA)    C63N32D630 (50kA)    C63N35E630  (50kA)   C63N36E630 (50kA)   C63H32D630 (70kA)   C63H35E630 (70kA)   C63H36E630 (70kA)

LC1G630KUEN



Selection of motor protection switch and contactor according to motor power